CO13XXL - MANAGEMENT AND CONTROL OF EMERGENCY STOPS
Control of emergency stops
Safety management in a compact 22.5 mm format
Mono or two-channel with wiring. "Low consumption" Inputs
Removable terminals
Performance level with AWAX controller: PL = d
Safety category: 3 (two-channel)
afety Integrity Level: SIL 2
Time before dangerous failure: MTTFd = 240 years
Cycle before dangerous failure: B10d=100,000 at 5A
Risk duration: 20 ms max.
Cable severing protection: yes (opening of safety lines)
Safety contacts/diagnostics: 2x NO 8A/250V redundant / 1x NF 8A/250V parallel redundant + 1x NO static 400 mA
Indicators: 3 LEDs for diagnostics
Reset: configurable by dip-switch (SR=Automatic, N=manual)
Mounting: symmetrical DIN 35mm rail on DIN 50022
Mounting: IP 20 electrical box
Electrical connection: Maximum 14 AWG (2.08 mmò) / 250V minimum
Temperature: -20ðC to +60ðC
ISAC ENTERPRISES
All Rights Reserved.(Terms of Use) Developed and Managed by Infocom Network Private Limited. |